Humidity control glossary
Short explanations of the terms used when selecting dehumidifiers and designing humidity control systems: relative humidity, dew point, moisture load, refrigerant dehumidifiers, desiccant dehumidifiers, dry rooms.
Properties of moist air
- Relative humidity (%RH)
- The ratio between the water vapour in the air and the maximum the air can hold at the same temperature, in %. For the same amount of vapour, colder air has a higher %RH, so a %RH figure without a temperature is not enough to select a dehumidifier.
- How to measure humidity in your plant
- Humidity ratio (g/kg)
- The mass of water vapour (grams) in 1 kg of dry air. Engineers use it to calculate moisture loads because it does not change when air is heated or cooled (as long as no condensation occurs).
- Dew point (°C)
- The temperature at which water vapour in the air starts to condense. Any surface colder than the dew point of the surrounding air gets wet: ceilings, floors, ducts, packaging, products. Dry rooms for lithium batteries are specified by dew point instead of %RH.
- Wet-bulb temperature
- The temperature read by a thermometer whose bulb is wrapped in wet cloth. The drier the air, the faster water evaporates and the further the wet bulb falls below the ordinary (dry-bulb) temperature. Dry-bulb and wet-bulb readings together fully describe the state of moist air.
- Psychrometric chart
- A chart showing how air temperature, relative humidity, humidity ratio, dew point and enthalpy relate. Engineers use it to plot treatment processes: cooling, dehumidifying, heating and mixing with outdoor air.
- Moisture load (kg/h)
- The amount of water vapour that must be removed from a space each hour to hold the target humidity. It comes from outdoor air and infiltration through doors, moisture diffusing through walls and floors, people, products and production processes. Select equipment by the calculated moisture load, not by floor area.
- Estimate the moisture load
Principles and equipment
- Refrigerant (compressor) dehumidifier
- A fan draws humid air across an evaporator coil colder than the dew point, so water vapour condenses and drains away; the dried air then passes the condenser coil to be rewarmed before returning to the room. Suitable for holding about 40–60 %RH at normal temperatures, such as warehouses, workshops and equipment rooms. HARISON dehumidifiers work on this principle.
Video: how a refrigerant dehumidifier works
- HARISON dehumidifiers
- DryMax desiccant dehumidifier
- Air passes through a honeycomb wheel (rotor) impregnated with silica gel adsorbent; water vapour is held on the silica gel surface, so the air leaves very dry. The rotor turns slowly and one sector is swept by hot air that drives the moisture out (reactivation) before it returns to dehumidifying. Desiccant units reach low humidity and low dew points that compressor units cannot, even at low room temperatures.
- DryMax standard DM series
- Adsorption vs absorption
- Adsorption: water molecules attach to the surface of a porous solid such as silica gel, and the solid does not change state. Absorption: the desiccant takes water into its bulk, typically a salt solution such as lithium chloride, and its properties change as it takes up water. DryMax silica gel rotors work by adsorption.
- Desiccant rotor
- A honeycomb wheel made of heat-resistant material and impregnated with adsorbent; the core component of a desiccant dehumidifier. Rotor quality determines the unit's capacity, service life and fire resistance.
- Process air and reactivation air
- Process air is the airstream that passes through the larger sector of the rotor to be dried and supplied to the room. Reactivation air is a smaller airstream, heated (electric, steam or recovered heat), that flows the opposite way through the remaining sector to carry the moisture outside.
- Outdoor air (OA) treatment
- Outdoor air in Vietnam is usually hot and very humid and is the largest moisture load in many plants. Outdoor air treatment cools and dehumidifies it before it enters the workshop, keeping humidity stable and reducing the load on the air-conditioning system.
- Outdoor air solutions for factories
- Humidifiers
- Equipment that adds water vapour to the air when humidity is too low, for example in electronics cleanrooms, paper stores and textile mills in the dry season. The goal is still to hold humidity within a stable range.
- HUMAX humidifiers
- External static pressure (ESP)
- The fan pressure left over to overcome the resistance of ducts, grilles and accessories outside the unit, in Pa. If the ESP is insufficient, the actual airflow falls below design and dehumidification suffers.
Applications and projects
- Dry room
- A production room kept extremely dry, specified by a dew point several tens of degrees below zero °C, used for lithium battery manufacturing and some moisture-sensitive pharmaceuticals. It requires a dedicated desiccant dehumidifier, an airtight room and control of moisture from people and materials.
- Lithium battery dry room solutions
- Cleanrooms
- A room in which particle count, temperature, humidity and pressure differential are controlled to a cleanliness class. Wrong humidity makes pharmaceutical powders clump and damages electronic components through static or corrosion.
- Cleanroom solutions
- Condensation
- Water forming on surfaces colder than the dew point of the surrounding air, such as cold-store ceilings, seafood plant ceilings and chilled-water pipes. The fix is to lower the air's dew point below the surface temperature, not just to blow air over it.
- "Nồm" (spring humidity)
- Late-winter, early-spring weather in northern Vietnam when warm, humid air meets walls and floors still cold from a cold spell, so vapour condenses and surfaces become wet. Keep doors closed and run dehumidifiers; opening windows for ventilation during nồm makes it worse.
- Low-temperature drying
- Drying with dehumidified air at moderate rather than high temperature, preserving the colour, aroma and nutrients of farm produce, food and herbs, and reducing cracking and warping in timber.
- Agricultural drying solutions
- Factory Acceptance Test (FAT)
- Running and inspecting equipment at the manufacturing plant before delivery, witnessed by the owner or consultant. DryMax equipment undergoes FAT at the DryMax factory in Cu Chi.