Scope
Scheduled maintenance of HARISON HD-504B and HD-100BM dehumidifiers in the production rooms of an electronic-component plant, measuring inlet and outlet air on each unit.
The customer's problem
Component production rooms need dehumidifiers running steadily all the time; dust build-up or low refrigerant cuts capacity in ways that are hard to see.
ENCO's solution
Coil cleaning, refrigerant and electrical checks, and inlet/outlet temperature and humidity measurement to confirm each unit's capacity, with a report per unit.
Results
- Inlet air: 23.4 °C, 47.6 %RH
- Outlet air: 33.4 °C, 20.2 %RH. The outlet air has been warmed by 10 °C by the unit's condenser, so its %RH is low; the room itself is still held at the set humidity, not at 20 %RH
- Calculated from the readings: the air's dew point drops from about 11.7 °C to about 7.5 °C, i.e. the unit is removing water vapour from the air