Electronics · maintenance

HARISON dehumidifier maintenance for an electronic components plant: inlet and outlet air measured to confirm rated performance

Hai Phong2022

Scope

Scheduled maintenance of HARISON HD-504B and HD-100BM dehumidifiers in the production rooms of an electronic-component plant, measuring inlet and outlet air on each unit.

The customer's problem

Component production rooms need dehumidifiers running steadily all the time; dust build-up or low refrigerant cuts capacity in ways that are hard to see.

ENCO's solution

Coil cleaning, refrigerant and electrical checks, and inlet/outlet temperature and humidity measurement to confirm each unit's capacity, with a report per unit.

Results

  • Inlet air: 23.4 °C, 47.6 %RH
  • Outlet air: 33.4 °C, 20.2 %RH. The outlet air has been warmed by 10 °C by the unit's condenser, so its %RH is low; the room itself is still held at the set humidity, not at 20 %RH
  • Calculated from the readings: the air's dew point drops from about 11.7 °C to about 7.5 °C, i.e. the unit is removing water vapour from the air
HARISON dehumidifier maintenance for an electronic components plant: inlet and outlet air measured to confirm rated performance

Photos from the site

HARISON HD-504B in a component production room
HARISON HD-504B in a component production room
Inlet air: 47.6 %RH at 23.4 °C
Inlet air: 47.6 %RH at 23.4 °C
Outlet air: 20.2 %RH at 33.4 °C (air has been warmed)
Outlet air: 20.2 %RH at 33.4 °C (air has been warmed)